Oscar Sondermeijer, Roel Dobbe|arXiv (Cornell University)|Feb 20, 2019
Optimal Power Flow DistributionEngineering3 references33 citations
TL;DR

The paper presents a data-driven, fully decentralized method that uses regression to map local inverter measurements to near-optimal reactive power injections, achieving close-to-optimal OPF-like performance without real-time communication. It demonstrates coordination with legacy equipment and potential to flatten voltages and reduce losses.

ABSTRACT

Electronic power inverters are capable of quickly delivering reactive power to maintain customer voltages within operating tolerances and to reduce system losses in distribution grids. This paper proposes a systematic and data-driven approach to determine reactive power inverter output as a function of local measurements in a manner that obtains near optimal results. First, we use a network model and historic load and generation data and do optimal power flow to compute globally optimal reactive power injections for all controllable inverters in the network. Subsequently, we use regression to find a function for each inverter that maps its local historical data to an approximation of its optimal reactive power injection. The resulting functions then serve as decentralized controllers in the participating inverters to predict the optimal injection based on a new local measurements. The method achieves near-optimal results when performing voltage- and capacity-constrained loss minimization and voltage flattening, and allows for an efficient volt-VAR optimization (VVO) scheme in which legacy control equipment collaborates with existing inverters to facilitate safe operation of distribution networks with higher levels of distributed generation.

Motivation & Objective

  • Motivate voltage regulation challenges in distribution grids with high distributed generation.
  • Propose a decentralized control framework that computes near-optimal inverter reactive injections using local data.
  • Leverage offline OPF and regression to design local controllers without real-time communication.
  • Demonstrate collaboration potential with legacy devices (LTCs, capacitor banks) and assess performance.
  • Show case study on a realistic feeder to validate near-optimality and coordination capabilities.

Proposed method

  • Compute globally optimal reactive injections for all inverters via convex OPF across N historical scenarios.
  • For each inverter, fit a multiple linear regression mapping local measurements to its optimal reactive injection.
  • Use a stepwise selection to pick predictive local variables and interactions that maximize prediction quality.
  • Implement the resulting regression models as decentralized controllers relying only on local measurements.
  • Evaluate performance in simulation against three baselines: no VAR, constant power-factor operation, and regression-based control.
  • Demonstrate potential collaboration with a substation LTC to flatten voltages while safely lowering overall voltage.

Experimental results

Research questions

  • RQ1Can regression-based local controllers reproduce near-optimal reactive injections obtained from a centralized OPF?
  • RQ2What is the accuracy of the regression models in predicting optimal inverter injections across diverse loading/generation scenarios?
  • RQ3Can the decentralized controllers maintain voltage within constraints and reduce losses without real-time communication?
  • RQ4How does collaboration with substation LTC impact voltages and losses when using regression-based inverter control?

Key findings

  • The regression-based approach yields near-optimal objective values, with maximum deviation 1.6% and average deviation 0.15% from the optimal.
  • Approach c (regression-based control) achieves better performance than no VAR or constant power-factor operation across the test period.
  • The regression-based method significantly reduces substation reactive power injections, indicating local sourcing of reactive power from PV inverters and improved substation PF.
  • Voltages across the feeder under regression-based control remain close to nominal values, with reduced voltage variability compared to baselines.
  • Collaboration with a load tap changer (LTC) can further lower overall feeder voltage while preserving voltage stability and loss reduction.
  • Inverter A and B show different predictive features, illustrating the need for inverter-specific regression models.

Read this paper