[Paper Review] Transforming Cooling Optimization for Green Data Center via Deep Reinforcement Learning
This paper proposes an end-to-end deep reinforcement learning (DRL) framework, Cooling Control Algorithm (CCA), based on the actor-critic and off-policy DDPG algorithm to optimize data center cooling by directly learning from monitoring data. The method achieves 11% cooling energy savings in simulation and up to 15% in real trace-based evaluation using a de-underestimation validation mechanism to ensure conservative and reliable performance estimation.
Cooling system plays a critical role in a modern data center (DC). Developing an optimal control policy for DC cooling system is a challenging task. The prevailing approaches often rely on approximating system models that are built upon the knowledge of mechanical cooling, electrical and thermal management, which is difficult to design and may lead to sub-optimal or unstable performances. In this paper, we propose utilizing the large amount of monitoring data in DC to optimize the control policy. To do so, we cast the cooling control policy design into an energy cost minimization problem with temperature constraints, and tap it into the emerging deep reinforcement learning (DRL) framework. Specifically, we propose an end-to-end cooling control algorithm (CCA) that is based on the actor-critic framework and an off-policy offline version of the deep deterministic policy gradient (DDPG) algorithm. In the proposed CCA, an evaluation network is trained to predict an energy cost counter penalized by the cooling status of the DC room, and a policy network is trained to predict optimized control settings when gave the current load and weather information. The proposed algorithm is evaluated on the EnergyPlus simulation platform and on a real data trace collected from the National Super Computing Centre (NSCC) of Singapore. Our results show that the proposed CCA can achieve about 11% cooling cost saving on the simulation platform compared with a manually configured baseline control algorithm. In the trace-based study, we propose a de-underestimation validation mechanism as we cannot directly test the algorithm on a real DC. Even though with DUE the results are conservative, we can still achieve about 15% cooling energy saving on the NSCC data trace if we set the inlet temperature threshold at 26.6 degree Celsius.
Motivation & Objective
- To address the challenge of sub-optimal or unstable cooling control in data centers due to complex, hard-to-model thermal and mechanical dynamics.
- To develop a data-driven, end-to-end control policy that bypasses the need for detailed system modeling.
- To reduce cooling energy consumption while maintaining temperature constraints in real-world data center environments.
- To validate the proposed method on both simulation and real-world data traces, ensuring practical feasibility.
- To introduce a de-underestimation (DUE) validation mechanism to prevent overly optimistic energy saving estimates in real-world deployment.
Proposed method
- The CCA framework uses an actor-critic deep reinforcement learning architecture to learn a control policy directly from historical monitoring data.
- It employs an off-policy offline version of the Deep Deterministic Policy Gradient (DDPG) algorithm to improve sample efficiency and training stability.
- An evaluation network (critic) predicts energy cost with penalties for non-compliant cooling states, while a policy network (actor) outputs optimized control actions based on current load and weather inputs.
- The reward function is designed to minimize energy cost while enforcing temperature constraints, with a penalty term controlled by hyperparameter λ.
- A de-underestimation (DUE) validation method is introduced, replacing standard square error with a loss that only penalizes underestimation of temperature to avoid overly optimistic results.
- The method is evaluated on the EnergyPlus simulation platform and a real data trace from the National Super Computing Centre (NSCC), using state features including rack power, flow rates, and supply temperatures.
Experimental results
Research questions
- RQ1Can an end-to-end deep reinforcement learning approach outperform traditional two-stage model-based optimization in data center cooling?
- RQ2How well can a DRL-based policy generalize to real-world data when direct deployment is not feasible?
- RQ3What impact does the choice of penalty hyperparameter λ have on the trade-off between energy savings and temperature compliance?
- RQ4Can a de-underestimation (DUE) validation method provide more reliable and conservative performance estimates than standard validation?
- RQ5To what extent can the learned policy reduce cooling energy consumption while maintaining safe rack inlet temperatures?
Key findings
- The CCA algorithm achieved approximately 11% cooling energy savings compared to a manually configured baseline in the EnergyPlus simulation platform.
- On the real NSCC data trace, the algorithm achieved up to 15% cooling energy savings when the inlet temperature threshold was set at 26.6°C, using the DUE validation method.
- The DUE validation method effectively reduced underestimation bias in temperature prediction, leading to more conservative and trustworthy performance estimates.
- As λ increased, energy savings decreased while maximum rack temperature was reduced, indicating a tunable trade-off between efficiency and thermal safety.
- The DRL model successfully captured system dynamics, with a mean absolute error (MAE) of less than 0.1°C in temperature prediction, even under noisy real-world data.
- The policy network demonstrated robustness in predicting optimal airflow rates across varying load and weather conditions, as validated through trace-based testing.