This study proposes a novel fault location estimation method for mixed overhead and underground cable transmission lines using image processing of R-X impedance diagrams from distance protection relays. By extracting features from fault-generated images and applying artificial neural networks (ANN) and regression models, the approach achieves high-accuracy fault location prediction—with errors below 1.3%—demonstrating that image processing enhances fault location accuracy in complex mixed-line systems.
The distance protection relays are used to determine the impedance based fault location according to the current and voltage magnitudes in the transmission lines. However, the fault location cannot be correctly detected in mixed transmission lines due to different characteristic impedance per unit length because the characteristic impedance of high voltage cable line is significantly different from overhead line. Thus, determinations of the fault section and location with the distance protection relays are difficult in the mixed transmission lines. In this study, 154 kV overhead transmission line and underground cable line are examined as the mixed transmission line for the distance protection relays. Phase to ground faults are created in the mixed transmission line. overhead line section and underground cable section are simulated by using PSCAD-EMTDC.The short circuit fault images are generated in the distance protection relay for the overhead transmission line and underground cable transmission line faults. The images include the R-X impedance diagram of the fault, and the R-X impedance diagram have been detected by applying image processing steps. Artificial neural network (ANN) and the regression methods are used for prediction of the fault location, and the results of image processing are used as the input parameters for the training process of ANN and the regression methods. The results of ANN and regression methods are compared to select the most suitable method at the end of this study for forecasting of the fault location in transmission lines.
Motivation & Objective
- To address the challenge of inaccurate fault location estimation in mixed transmission lines due to differing characteristic impedances between overhead and underground cables.
- To develop a fault location estimation system that distinguishes between fault locations in overhead line and underground cable sections of mixed lines.
- To evaluate and compare the performance of artificial neural networks (ANN) and regression models using image-processed fault data for improved fault location accuracy.
- To demonstrate the feasibility and effectiveness of integrating image processing techniques into traditional distance protection relays for enhanced fault location prediction.
Proposed method
- Simulated a 154 kV mixed transmission line with overhead and underground cable sections using PSCAD/EMTDC to generate short-circuit fault data.
- Generated R-X impedance diagrams from fault current and voltage measurements in the distance protection relay, treating them as digital images.
- Applied image processing techniques to extract features from the R-X impedance diagrams, transforming them into structured input data for machine learning models.
- Trained multiple artificial neural network architectures (e.g., Feed Forward Backpropagation with Levenberg-Marquardt, Cascade Feedforward, Elman Feedback) using the image-processed features.
- Trained and compared various regression models (e.g., Linear Regression, Stepwise Linear, SVM, Gaussian Process Regression, Ensemble Trees) using the same image-derived features.
- Used RMSE (Root Mean Square Error) as the primary metric to evaluate and compare the performance of all models across both overhead and underground cable sections.
Experimental results
Research questions
- RQ1Can image processing of R-X impedance diagrams from distance protection relays improve fault location estimation accuracy in mixed overhead and underground cable transmission lines?
- RQ2Which machine learning model—ANN or regression—performs better for fault location estimation when using image-processed fault data in mixed transmission lines?
- RQ3How does the fault location estimation error vary between overhead line and underground cable sections in a mixed transmission line configuration?
- RQ4To what extent can image-processed features from fault-generated R-X diagrams enhance the predictive capability of fault location models?
Key findings
- The Feed Forward Backpropagation Levenberg-Marquardt (LM) neural network achieved the lowest training error (RMSE = 0.0048) for fault location estimation in the overhead line section.
- For the underground cable section, Stepwise Linear Regression produced the best performance with the lowest RMSE (0.0060709) among all regression models tested.
- The maximum percentage error in fault location estimation was 1.28% for the overhead line and 1.304% for the underground cable line, indicating high predictive accuracy.
- Image-processed features from R-X diagrams significantly improved fault location estimation, with the best-performing models achieving sub-1.3% error across both line types.
- The study demonstrated that different optimal models are required for overhead and underground cable sections, with ANN outperforming regression in overhead lines and regression in underground lines.
- The integration of image processing into traditional distance protection relays enables accurate fault section and location identification in mixed transmission lines, overcoming limitations due to impedance mismatch.