[Paper Review] Maximum Marginal Likelihood Estimation of Phase Connections in Power Distribution Systems

Wenyu Wang, Nanpeng Yu|arXiv (Cornell University)|Feb 26, 2019
Power System Optimization and StabilityEngineering7 citations
TL;DR

This paper proposes a maximum marginal likelihood estimation (MMLE)-based method for phase connection identification in power distribution systems using smart meter data. By linearizing the three-phase power flow manifold, the method formulates phase identification as a physically interpretable MMLE problem, solving it via binary least-squares subproblems. It achieves over 96% accuracy on complex radial and meshed networks, outperforming existing data-driven methods under incomplete measurements and model inaccuracies.

ABSTRACT

Accurate phase connectivity information is essential for advanced monitoring and control applications in power distribution systems. The existing data-driven approaches for phase identification lack precise physical interpretation and theoretical performance guarantee. Their performance generally deteriorates as the complexity of the network, the number of phase connections, and the level of load balance increase. In this paper, by linearizing the three-phase power flow manifold, we develop a physical model, which links the phase connections to the smart meter measurements. The phase identification problem is first formulated as a maximum likelihood estimation problem and then reformulated as a maximum marginal likelihood estimation problem. We prove that the correct phase connection achieves the highest log likelihood values for both problems. An efficient solution method is proposed by decomposing the original problem into subproblems with a binary least-squares formulation. The numerical tests on a comprehensive set of distribution circuits show that our proposed method yields very high accuracy on both radial and meshed distribution circuits with a combination of single-phase, two-phase, and three-phase loads. The proposed algorithm is robust with respect to inaccurate feeder models and incomplete measurements. It also outperforms the existing methods on complex circuits.

Motivation & Objective

  • Address the lack of theoretical guarantees and physical interpretability in existing data-driven phase identification methods for distribution systems.
  • Improve phase identification accuracy in complex networks with mixed single-phase, two-phase, and three-phase loads, especially in meshed configurations.
  • Ensure robustness to incomplete smart meter coverage and inaccurate feeder models, which degrade performance in prior approaches.
  • Develop a computationally efficient algorithm that maintains high accuracy under real-world measurement and modeling uncertainties.
  • Provide a theoretically grounded framework that establishes the correct phase connection as the global optimum for both maximum likelihood and marginal likelihood estimation.

Proposed method

  • Linearize the three-phase power flow manifold to derive a physical model linking phase connections to smart meter measurements.
  • Formulate the phase identification problem as a maximum likelihood estimation (MLE) problem, proving that the correct phase connection maximizes the log-likelihood.
  • Reformulate the MLE problem as a maximum marginal likelihood estimation (MMLE) problem to improve tractability, with the correct connection still yielding the highest marginal log-likelihood.
  • Decompose the MMLE problem into smaller subproblems using a voting and target-only strategy, enabling efficient solution via binary least-squares optimization.
  • Transform each subproblem into an equivalent binary least-squares form and solve via convex relaxation of binary constraints, preserving solution quality.
  • Use iterative refinement and consensus from subproblem solutions to determine the global phase connection assignment.

Experimental results

Research questions

  • RQ1Can a data-driven phase identification method be grounded in physical power flow principles to ensure theoretical performance guarantees?
  • RQ2Does the proposed MMLE formulation yield the correct phase connection as a global optimum under realistic distribution system conditions?
  • RQ3How does the proposed method perform on complex, heavily meshed distribution networks with mixed load types compared to existing correlation- and clustering-based approaches?
  • RQ4To what extent is the method robust to incomplete smart meter coverage and inaccurate feeder models?
  • RQ5Can the MMLE formulation be efficiently solved at scale while maintaining high accuracy in real-world distribution test systems?

Key findings

  • The proposed MMLE-based method achieves 100% phase identification accuracy on the 37-bus radial feeder with 0.1% smart meter measurement accuracy over 90 days.
  • On the 123-bus radial feeder, the method maintains over 96% accuracy at 70% smart meter penetration and exceeds 96% accuracy even at 10% penetration, outperforming benchmark methods.
  • On the complex 342-bus meshed feeder, the method achieves 96.63% accuracy at 0.1% measurement class and 99.52% at 90 days with 0.2% class meters, significantly outperforming correlation- and clustering-based methods.
  • The method is more robust to incomplete measurements on the 342-bus meshed network than on the 123-bus radial system due to higher sensitivity of voltage measurements to local phase decisions.
  • The algorithm remains effective under noisy network parameters (30% deviation in line admittance) and missing topology information (8 branches omitted), demonstrating strong robustness.
  • The MMLE formulation ensures that the correct phase connection is the global optimum, as proven theoretically, providing a solid foundation for data-driven phase identification.

Read this paper

Open the full text in the Nubint reader and ask about any passage as you read.

Read this paper on Nubint