[Paper Review] Multiple Ancillary Services Provision by Distributed Energy Resources in Active Distribution Networks
This paper proposes a centralized model predictive control (MPC)-based controller that enables heterogeneous distributed energy resources (DERs) in active distribution networks to concurrently provide voltage support, primary, and secondary frequency control. By leveraging an input-multirate framework and network decomposition of a linear power flow model, the controller efficiently manages multiple timescales and network constraints, achieving accurate ancillary service provision with under 3% error and significantly improved computation times in simulations on the IEEE 33-bus system.
The electric power system is currently experiencing radical changes stemming from the increasing share of renewable energy resources and the consequent decommissioning of conventional power plants based on synchronous generators. Since the principal providers of ancillary services are being phased out, new flexibility and reserve providers are needed. The proliferation of Distributed Energy Resources (DERs) in modern distribution networks has opened new possibilities for distribution system operators, enabling them to fill the market gap by harnessing the DER flexibility. This paper introduces a novel centralized MPC-based controller that enables the concurrent provision of voltage support, primary and secondary frequency control by adjusting the setpoints of a heterogeneous group of DERs in active distribution grids. The input-multirate control framework is used to accommodate the distinct timescales and provision requirements of each ancillary service and to ensure that the available resources are properly allocated. Furthermore, an efficient way for incorporating network constraints in the formulation is proposed, where network decomposition is applied to a linear power flow formulation together with network reduction. In addition, different timescale dynamics of the employed DERs and their capability curves are included. The performance of the proposed controller is evaluated on several case studies via dynamic simulations of the IEEE 33-bus system.
Motivation & Objective
- To address the growing need for ancillary services as conventional synchronous generators are phased out due to decarbonization efforts.
- To harness the untapped flexibility of diverse DERs—such as BESS, PVs, DGs, and flexible loads—in active distribution networks.
- To develop a centralized control framework that coordinates multiple ancillary services (voltage support, primary and secondary frequency control) with distinct timescales and requirements.
- To incorporate network constraints, including thermal limits and voltage limits, into the control formulation without sacrificing computational efficiency.
- To evaluate the controller’s performance under dynamic disturbances such as generator loss and line trips, ensuring system stability and secure operation.
Proposed method
- An input-multirate MPC framework is employed to handle the distinct timescales of primary (fast), secondary (medium), and voltage (slow) frequency control.
- The controller uses a linearized power flow model with network decomposition and network reduction techniques to reduce problem dimensionality and improve computational efficiency.
- The optimization problem includes constraints on active and reactive power limits, voltage magnitude, and branch thermal limits, derived from DER capability curves and system dynamics.
- The controller dynamically adjusts DER setpoints based on real-time signals from the transmission system operator, ensuring power exchange at the point of common coupling tracks scheduled values.
- A cost function is formulated to minimize control effort and deviation from scheduled power flows, with penalty terms for voltage violations and network congestion.
- The controller accounts for dynamic system behavior, including frequency deviations and voltage drops due to contingencies, by integrating real-time feedback and predictive control.
Experimental results
Research questions
- RQ1How can a centralized controller effectively coordinate multiple ancillary services—voltage support, primary, and secondary frequency control—across heterogeneous DERs with different response times?
- RQ2What is the impact of network constraints such as thermal limits and voltage violations on the feasible operating region of DERs in active distribution networks?
- RQ3How does the proposed network decomposition and linear power flow formulation affect computational efficiency and solution accuracy compared to full system modeling?
- RQ4Can the controller maintain system stability and meet service requirements during large disturbances such as generator loss or line trips?
- RQ5What is the trade-off between control performance, computational load, and the use of network constraints in DER dispatch?
Key findings
- The proposed controller successfully coordinates multiple ancillary services in real time, with the voltage magnitude at bus 1 settling at the desired steady-state value governed by the control law.
- During a contingency involving a generator outage, the controller responded within one time step by injecting approximately 0.4 p.u. of reactive power to counteract voltage drop, with minor overshoot corrected in the next step.
- Branch (17,18) reached its thermal limit due to reverse power flow from high PV injection, demonstrating that network bottlenecks constrain DER utilization.
- The network decomposition method introduced less than 3% error in power flow calculations while significantly reducing computation time, enhancing scalability.
- The controller accurately restored active power exchange at the PCC after disturbances by adjusting DER active power setpoints, as enforced by constraints (31) and (33).
- The controller’s performance was validated under both steady-state and dynamic conditions, showing robustness to voltage disturbances and frequency deviations.
Read this paper