TL;DR

The paper presents a physics-informed offline reinforcement learning framework (TTDM) with a graph neural network and time-reversal symmetry constraints to optimize data center cooling, achieving 14–21% energy savings in real production DCs without safety violations.

ABSTRACT

The recent advances in information technology and artificial intelligence have fueled a rapid expansion of the data center (DC) industry worldwide, accompanied by an immense appetite for electricity to power the DCs. In a typical DC, around 30~40% of the energy is spent on the cooling system rather than on computer servers, posing a pressing need for developing new energy-saving optimization technologies for DC cooling systems. However, optimizing such real-world industrial systems faces numerous challenges, including but not limited to a lack of reliable simulation environments, limited historical data, and stringent safety and control robustness requirements. In this work, we present a novel physics-informed offline reinforcement learning (RL) framework for energy efficiency optimization of DC cooling systems. The proposed framework models the complex dynamical patterns and physical dependencies inside a server room using a purposely designed graph neural network architecture that is compliant with the fundamental time-reversal symmetry. Because of its well-behaved and generalizable state-action representations, the model enables sample-efficient and robust latent space offline policy learning using limited real-world operational data. Our framework has been successfully deployed and verified in a large-scale production DC for closed-loop control of its air-cooling units (ACUs). We conducted a total of 2000 hours of short and long-term experiments in the production DC environment. The results show that our method achieves 14~21% energy savings in the DC cooling system, without any violation of the safety or operational constraints. Our results have demonstrated the significant potential of offline RL in solving a broad range of data-limited, safety-critical real-world industrial control problems.

Motivation & Objective

  • Address the high energy cost of data center cooling by developing data-efficient, safe optimization methods.
  • Leverage offline historical data to learn policies without high-fidelity simulators or online exploration.
  • Incorporate physics knowledge via time-reversal symmetry and graph neural networks to improve generalization.
  • Deploy and validate in real-world production data centers and a dedicated testbed.

Proposed method

  • Formulate DC cooling control as an offline MDP with a safety-aware reward balancing energy use and temperature safety.
  • Develop TTDM: a T-symmetry enforced thermal dynamics model using a graph neural network to capture spatial and control dependencies.
  • Impose latent ODE forward and reverse dynamics to enforce T-symmetry in a compact latent space.
  • Train Q-functions and policies in the latent space with TD3+BC style objectives and a T-symmetry regularization loss.
  • Use a reconstruction and physics-consistent loss to learn robust latent representations (Lrec,Lfwd,Lrvs,Lds,LT-sym).
  • Evaluate on real production DCs (2000 hours) and a 22-server testbed, comparing to PID and other offline/RL baselines.

Experimental results

Research questions

  • RQ1Can physics-informed offline RL learn effective, safe control policies for DC cooling from limited historical data without simulators?
  • RQ2Does enforcing T-symmetry and using a GNN-based dynamics model improve offline RL data efficiency and OOD generalization in DC cooling?
  • RQ3What is the achievable energy savings and thermal safety performance when deploying offline RL policies in real production DCs?
  • RQ4How does controlling more ACUs impact energy efficiency under varying server loads?
  • RQ5How do ablations of GNN structure and T-symmetry enforcement affect prediction error and policy performance?

Key findings

  • Achieves 14–21% energy savings in DC cooling compared with standard PID controllers in real production DCs.
  • Maintains thermal safety with no CAT violations during 2000 hours of deployment.
  • Long-term experiments show consistent ACLF reductions and improved temperature field uniformity under load fluctuations.
  • Testbed and ablation results demonstrate that incorporating GNN structure and T-symmetry enforcement reduces multi-step prediction error and enhances policy performance.
  • Outperforms baseline methods (PID, MPC, off-policy RL baselines, and safe offline RL) in energy efficiency while preserving safety in a data-limited setting.

Read this paper

Open the full text in the Nubint reader and ask about any passage as you read.

Read this paper on Nubint

This review was generated by AI from the original paper. Please check the paper before citing it.